START STRATEGY 1:
- do note that overall width of s/c would be based on the most stringent floor load, x. so if auditorium on L8, with the most OL, L1-L7 s/c would need to also cater of OL x, with " no reduction in width, regardless of lower stories having less number of occupants".
So highest OL function, usually on lower floors. Clause 2.2.3
Occupancy load does not include ( non-simultaneous space)
- eg corridors, pantries, lift lobbies
Capacity: Note doorway/ corridor/ staircase
2) Placement of staircase
Condition 1
Condition 1
- remoteness cannot be < 1/2 D, or 1/3D ( if sprinkled)
Designer thought: that means storey building with a service core in the middle is interesting to see how their staircase fulfill the 1/2 D; 1/3D or maybe that would determine the floor plate size.
Eg in a 10x10 floorplate, distance between 2 stairs, as a sprinkled building has to be at least 3m apart..
To Think: About worse case scenario for a fire, and which s/c is available to run to, and if it can take the OL
Condition 2
Designer thought: that means storey building with a service core in the middle is interesting to see how their staircase fulfill the 1/2 D; 1/3D or maybe that would determine the floor plate size.
Eg in a 10x10 floorplate, distance between 2 stairs, as a sprinkled building has to be at least 3m apart..
To Think: About worse case scenario for a fire, and which s/c is available to run to, and if it can take the OL
Condition 2
-travel distance ( note sprinkler protected or not) * note travel distance is to door of staircase, not door of SSL
--> if details known, measure 1 way ( measure from remote corner of partition room to center of external corridor when 2 way starts, 2 way
--> unknown 2/3 of D
Qn: Is allowable travel distance to the splitting point?
One way is measure until : it becomes 2 way, or when it reaches the door of s/c
Two way is measure from most remote to door of s/c
START STRATEGY 2:
Depending on width of staircase given & table 2.2 A, one can estimate how many people max for that floor plate.
Eg, for industrial purpose, for a 1m wide exit staircase, ( based on 1 unit width is 0.5m); 1 m wide is equivalent to 2 units widths; based on table 2.2A, gives 2x60 =120 pax
Calculation example
STOP AT PAGE 23/ 149